The following text and figures are from the GenTraco Transpanel
Installation Guide. This guide does not cover the Gen/Tran® transfer
switches. See the separate instructions for that product
line.

GenTraco Transpanel Installation Guide
NOTE: THE GENTRACO MANUAL TRANSFER PANEL SHOULD BE INSTALLED BY A QUALIFIED
ELECTRICIAN FAMILIAR WITH ALL APPLICABLE ELECTRICAL AND BUILDING CODES.
The GenTraco Transpanel is designed to provide a safe and simple method of
powering designated branch circuits from a portable generator in the event of a utility
power outage or emergency. The patented mechanical interlock between the two pole breakers
feeding the panel bus prevents feedback by prohibiting the GENERATOR SUPPLY breaker and
the UTILITY SUPPLY breaker from being "ON" at the same time.
These panels allow a homeowner to selectively power up any number or combination
of branch circuit breakers wired into the panel, up to the capacity of the generator.
INSTALLING THE GENTRACO MANUAL TRANSFER PANEL
Generally, the transfer panel should be located next to the main load center
(circuit breaker or fuse box).
- Install a large diameter nipple (2 inch trade size recommended) between the two
panels. If the main load center does not have a sub-feed lugs, a circuit breaker must be
installed in the same load center that is the same ampacity as the Utility Supply breaker
in the transfer panel.
- Run the proper ampacity wire between the two breakers.
- Run an insulated neutral wire from the neutral bars in both panels.
- If a non-metallic nipple was used in Step 1, then a ground wire must be run from
the neutral bars or ground terminal if separate from the neutral bar.
- The installer has the option of removing the selected branch circuit wire from
the main panel and reinstalling them in the transfer panel and connecting to the same
ampacity breaker as before, OR leaving the branch circuit wires in the main panel and
running the proper size wire from the transfer panel breaker to the circuit conductor in
the main panel.
- Remove the circuit conductor from the main panel circuit breaker and
"wire-nutted" to the wire coming from the transfer panel. This step must be done
for each circuit transferred to the transfer panel.
All GenTraco transfer panels are UL Listed with Siemens, Square D (HOM type),
GE, Challenger, and Westinghouse circuit breakers, however, other 1 -inch and 1/2 inch
interchangeable breakers will generally fit. If the main panel has these interchangeable
1-inch type breakers, they can be relocated to the transfer panel, HOWEVER, the cover in
the main panel MUST be fitted with blanks over the holes created by removing the breakers.
Continued...
KEY COMPONENTS OF THE GENTRACO TRANSFER PANEL
POWER INPUT SELECTOR BREAKERS: These double-pole breakers allow the selection of
either the "Utility Supply" or "Generator Supply" as the power source
for all of the circuits in the transfer panel. The patented interlocking mechanism
prevents both of these breakers from being 'ON" at the same time.
BRANCH CIRCUIT BREAKERS: These installer-furnished circuit breakers are of the 1
-inch or Y2-inch interchangeable style, and can be I - or 2-pole up to the ampacity of the
generator. Example: Installing a 2-pole 30 amp breaker for a water heater will use up the
entire capacity of a 7500 watt continuous duty generator. Therefore, all other circuits
would have to be turned off when the water heater is running. All of the breakers can be
"ON" when in the 'Utility Power" mode and selectively "ON" or
"OFF" in the generator mode.
The GenTraco Transfer Panel will accommodate up to 12 full-size 1 -inch breakers
or a combination of up to 4 full-size 1 -inch breakers and 16 half-size breakers.
WATTMETERS: