Automatic Transfer Switch
with integral residential load center
100 amp, 120/240V, 1-phase
generator exerciser
When you require a complete basic automatic transfer
transfer switch for handling only some of your branch circuits, we have the solution. The DynaGen Vigilant series
load center ATS includes a built-in sub-panel for up to 12 or 24 branch
circuits. It is designed to UL
1008 and has all the necessary delay timers, voltage sensing, frequency
sensing, and generator programmable
exerciser clock. Made in Canada.
Description
The Vigilant 100A Load Center Automatic Transfer Switch will save you
time and money on every installation. It completely eliminates the need
to install a separate sub-panel and gives you the option of installing 12
regular or 24 mini Square D circuit breakers (optionally supplied). And
no need to pull the power company meter for this type of ATS. Light
weight and easy to install, the Vigilant Load Center fits snugly between two
studs and has plenty of conveniently placed knockouts. It is so easy to
install that it can cut up to 3 hours off your installation time when compared
to installation of a regular transfer switch and separate sub-panel.
Specifications
| Switch Current Rating |
100 amps, 2 pole |
| Voltage Rating |
120/240V, 1 phase, 60Hz standard (50Hz
optional) |
| Branch Circuit Space |
12 full height breaker poles or
24 mini (half-height) breaker poles |
Control Features (see note 1)
KEY:
P.U. = pickup
D.O. = dropout |
Function |
Adjustable Range |
Factory Setting |
| start time delay |
0-32 sec |
10 sec |
| transfer time delay |
0-64 sec |
10 sec |
| retransfer time delay |
0-256 sec |
256 sec |
| cool down delay |
0-256 sec |
256 sec |
| |
|
|
| voltage sensing of utility |
11-18% D.O. above/below
6-13% P.U. above/below |
18%
13% |
| frequency sensing of utility |
5-12% above/below |
12% |
| voltage sensing of generator |
11-18% D.O. above/below
6-13% P.U. above/below |
18%
13% |
| frequency sensing of generator |
5-12% above/below |
12% |
| Exerciser Clock |
electronic design, field adjustable for 7 day
exercising with or without load transfer |
| Battery Charger |
not included (order separately if required) |
| UL Withstand & Closing Ratings |
22,000 amps when used with
properly rated 100A circuit breaker |
| Nominal Dimensions (H x W x D) |
26" x 14" x 6" |
| Weight |
45 lbs. |
| Warranty |
5 year factory warranty |
NOTES:
1) The start time delay prevents nuisance generator starts during momentary utility
power variations; transfer time delay allows generator set to stabilize before load is
applied; retransfer delay prevents needless power interruption if return of utility power
is momentary; stop delay allows gradual generator set cool down; undervoltage sensing of
utility supply provides reliable starting of generator set during brownout conditions.
2) This switch is not service entrance rated. This generally means that you
need a service entrance rated disconnect between this switch and your utility meter.