| Parameter |
Value |
| Secondary Surge Arrester Voltage Rating |
175V AC maximum, line to ground |
White Wire Length
(cut as short as possible) |
12 inches |
| Lead Lengths for Discharge Voltages |
1 inch / 6 inch |
| Discharge Voltage @ 1,500 amps |
500 / 575 V line to neutral |
| Discharge Voltage @ 5,000 amps |
625 / 725 V line to neutral |
| Discharge Voltage @ 10,000 amps |
750 / 1075 V line to neutral |
| Minimum Life for 1500 amp surges |
2,500 operations |
| Peak Single-Pulse Current Rating |
27,000 amps |
| Transient Energy Rating |
330 joules, line to neutral
660 joules, line to line |
| Operating Temperature Range |
-20 to 65 C (-4 to 150 F) |