Page last updated Oct 20, 2021 @ 10:42pm

Voltage Drop Calculator

Thanks for visiting NoOutage.com to use our free voltage drop calculator.

Check phone pricing on Cummins generators

While you are here please view our specials on all kinds of backup power related products such as...

* manual transfer switches

* automatic standby generators

* automatic transfer switches

* metering & instrumentation

* UPS systems


Tired of paying those rising electricity rates?  We also sell alternative energy products including...

* micro hydroelectric systems

* wind power systems

* solar

Are YOU ready for the next power outage?

Use this calculator to estimate cable voltage drop for sizing conductors.  The calculation assumes uncoated copper or aluminum conductors operating at the temperature selected and is based on the ac/dc resistance or impedance from NEC 2011 Chapter 9, Tables 8 and 9 for stranded conductors operating on a DC or AC 60Hz system. Rather than using the 'k' factor or the 'Effective Z' of Table 9 this method is based on the actual ac resistance and reactance values from the table. The load current input is fixed, as is the base system Voltage. The Voltage drop in the cable is calculated using Ohm's Law where Vdrop = Iload x Rcable. The percent drop is Vdrop / Vsystem x 100. For ac systems the ac impedance is used in place of the dc Rcable. This methodology is similar to the examples given after NEC Table 9.

The ampacity of each conductor size shown for reference in the dropdown menu below is based on NEC 2011 Table 310.15(B)(16) for 60C insulated conductors rated 0 through 2000 volts with not more than three current carrying conductors in raceway, cable or earth with an ambient of 30C (86F).

Note that the actual ampacity and voltage drop for your application may differ from these results but in most cases will be very close to those shown here.

Units herein are American Wire Gauge (AWG) and English (feet).

Note, to run this calculator JavaScripts must be enabled on your browser.

Click here for alternate calculator that also includes a transformer and motor load.


This should be the line-to-line voltage for multi-voltage and 3 phase systems.  For a 120/240V single phase system select 240V.  For other single phase systems select the line-to-neutral voltage.


These are uncoated copper or aluminum conductor sizes with CU/AL 60C Ampacity listed at 30C ambient for reference.


NEC ampacity tables assume 60C, 75C or 90C operating temperature. If conductor is oversized a lower temperature can be used. See NOTE 4. This value only used for adjusting conductor resistance.


See NOTE 1 below


Length of cable in feet (one-way distance)

 
Load current in amperes

   


Estimated voltage drop
See NOTE 2 below

 

 

NOTES:

  1. Examples for parallel runs: 120/240V single phase system with single black-red-white conductors (installed in single conduit) select "single set of conductors", 120/208V 3phase system with 2 conductors per phase and neutral (installed in 2 parallel conduits) select "2 conductors per phase in parallel", dc system with 3 positive and 3 negative conductors select "3 conductors per phase in parallel". 

  2. Voltage drop for ac systems should total no more than 5% under full load conditions.  This is recommended by the NEC 210.19(A)(1) Informational Note No. 4 which states a 3% limit for branch circuits and NEC 215.2(A)(4) Informational Note No. 2 which states a 3% limit for feeders. Both of these set a limit of 5% total for both.  Drop may be significantly larger during surge or motor starting conditions -- sometimes in the 15% to 25% range if other devices on the system can withstand this momentary dip.  Voltage drop for dc systems should be designed as low as possible or less than 2%.

  3. For most 120/240V systems using cables of adequate ampacity, voltage drop is not a concern unless cable lengths are well over a hundred feet.  A common rule of thumb is to check the voltage drop when the one-way circuit length in feet exceeds the system voltage number.  Therefore, using this rule one would check the drop for a 240V system if the circuit length exceeds 240 feet.

  4. For refining the calculation the conductor operating temperature can be estimated as follows: If the operating current equals the ampacity listed in NEC Tables 310.15 then the temperature can equal the rating of the table column. If the operating current is less than the ampacity listed then the temperature will be less. Since conductor heating is equal to the I2 x R losses, and the heating is proportional to the conductor temperature rise, then the operating temperature will be approximately (Ioperating / Iampacity)2 x (Trating - 30C) + 30C. For example, a 50 Amp load using 75C rated copper conductor requires #8 AWG per Table 310.15(B)(16). If the wire size is increased to #6 AWG for voltage drop considerations then the conductor operating temperature would be (50A / 65A)2 x (75C - 30C) + 30C = 57C. This results in a slight reduction of the voltage drop and may be useful for marginal calculations.

  5. All references to the NEC refer to National Fire Protection Association, NFPA 70®, National Electrical Code®. or National Electrical Code® Handbook.

More information about voltage drop based on IEC standards is available in the Schneider Electric Electrical Installation Guide.


UPDATE: On 11/4/2009 the 3-phase % calculation was adjusted by a factor of 1.732
UPDATE: On  9/25/2013 added #16 AWG; ac values extrapolated
UPDATE: On  4/27/2018 added 850V, 1000V and 1500V for dc solar systems
UPDATE: On 10/16/2018 added 70V, 80V, 90V for dc systems
UPDATE: On 02/25/2019 updated and added NEC references, expanded methodology description, added NOTE 4 and NOTE 5.
UPDATE: On   4/3/2019  added more Voltage choices between 120 and 208 for dc solar systems

 

 


Are YOU ready for the next power outage?

 1 Videos
 2 Outage Archives
 3 Utility Industry
 4 Why You Need Backup
 5 Personal Stories
 6 NoOutage Configurations
 7 Safety
 8 Sizing for Your Needs
 9 Voltage Drop Calculator
10 Test Reports
11 Placing Order
12 Equipment Leasing
13 Books & Videos  
14 Financing
15 Frequently Asked
16 Future Technologies
17 Electricity Glossary
18 Help with Plug Types
19 Who We Are
20 Why Buy Here
21 Our Customers
22 Pick a Contractor
23 Privacy Promise
24 Safe Shopping Guarantee
25 Terms & Conditions
26 What's New
27 Contacting Us
28 Parts Lookup
29 Parts & Service
30 Made in USA
31 Links

We welcome your feedback or questions.  Click here to contact us.
See our Terms & Conditions before using information or ordering from this web site.
Copyright © 1999-2023 NoOutage.com LLC.  All rights reserved.