Use this calculator to estimate cable voltage drop to
size conductors. The calculation assumes uncoated copper conductors
operating at a temperature 75C (140F) and is based on the largest ac/dc
resistance or impedance from NEC 2002 Tables 8 and 9. The allowable
ampacity of each conductor size in the dropdown menu below is based on NEC 2002
Table 310.16 for insulated conductors rated 0 through 2000 volts with not more
than three current carrying conductors in raceway, cable or earth with an
ambient of 30C (86F).
Note that the actual ampacity and voltage drop for your
application may differ from these results but in most cases will be better than
those shown here.
Units herein are American Wire Gauge (AWG) and
English (feet).
Note, to run this calculator JavaScripts must be enabled
on your browser.
Voltage drop for ac systems should total no
more than 5% under full load conditions. Drop may be significantly
larger during surge or motor starting conditions -- sometimes in the 15% to
25% range if other devices on the system can withstand this momentary
dip. Voltage drop for dc systems should be designed as low as possible
or less than 2%.
For most 120/240V systems using cables of
adequate ampacity voltage drop is not a concern unless cable lengths are well
over a hundred feet.
More information about voltage
drop based on IEC standards is available in the Schneider
Electric Electrical Installation Guide.