House UPS System
2400VA/2250 watt, 120VAC

 

Our House UPS systems fill a market niche between portable generators and automatic standby generators.  Most power outages last less than a couple hours and these systems easily provide backup AC power for that length of time.  These systems are silent and fully automatic and transfer extremely fast when line power is lost.  No more guessing how long an outage will last and whether it is worth the trouble to drag out that portable generator.  For most outages which are short this system eliminates that trouble!

For details about how this system operates and its advantages click here.

 

What is included in the NoOutage.com House UPS System?

We provide everything you need to install an operational system except for one circuit breaker that must be installed in your load center breaker panel and a connected wall outlet.  If you want to be able to provide backup power for a long-term power outage you will also need a portable generator (not included).  Make sure the generator has a high capacity 120V 30A NEMA L5-30R receptacle.  System includes the following:

* UPS Module 
* Transfer Switch - 4 circuit
* battery charger (in UPS)
* AC Input Cord - 25' with NEMA L5-30P Plug
* AC Output Cord with NEMA L5-30C
Connector
* interconnecting battery jumper cables
* gel cell maint-free lead acid batteries (in UPS)

We do not provide the circuit breaker for your load center panel due to the many brands of panels.  Purchase one locally that fits your panel.  It should be rated 30 amps.  Your installer will also need to wire this breaker to a 30A 120VAC NEMA L5-30R wall receptacle near the UPS.  

 

System Specs

System AC Line Input Voltage 120VAC nominal (77-152VAC limits)
System AC Line Input Frequency 60Hz +4Hz
AC Line Circuit Capacity 30 amps 120VAC minimum
Portable Generator Size (optional) 5000 Watts rated w/ 30 amp 120VAC receptacle and voltage regulator (recommended)  See NOTE 1
System DC Voltage & Battery Bank - see NOTE 3 120 VDC nominal
(10) 12V 5Ah internal batteries
(20) 12V batteries per external module
Inverter Power Output Rating 2400VA / 2250 Watts continuous
2650VA / 2500 Watts surge for 2 minutes
>2700VA / >2600 Watts for 0.2 seconds
see NOTE 2
System output voltage (on inverter) 120VAC +5%
pure sine wave
Automatic Transfer Time 4 milliseconds typical
System efficiency 95%
Approximate Battery Run-Time
See NOTE 4
internal battery only 500VA/450 watts average
1000VA/900 watts average
0.8 hours
0.4 hours
1 optional external battery module 500VA/450 watts average
1000VA/900 watts average
3.0 hours
1.52 hours
2 optional external battery modules 500VA/450 watts average
1000VA/900 watts average
5.2 hours
2.6 hours
3 optional external battery modules 500VA/450 watts average
1000VA/900 watts average
7.4 hours
3.7 hours
4 optional external battery modules 500VA/450 watts average
1000VA/900 watts average
9.5 hours
4.8 hours
Battery Charger Rating 6-10A at 120Vdc nominal (approx 1000 watts)
Approximate Battery Recharge Time Internal battery: 3 hours to 90% usable capacity
External Batteries: no more than 15X discharge time
Indicators (red/green/flash/audible alarm) - Power On LED
- Site wiring fault LED
- Battery Service LED
- On Battery LED
- General Alarm LED
- Load Level LEDs (5)
Communication Ports 
(work with included LanSafe software)
- RS232 DB9 Communication port with cable
  (factory installed in X-slot)
Surge Suppression
(active in both normal and bypass modes)
ANSI C62.41 Category B
IEC 61000-4-5 Level 3, Criteria B
Audible Noise (UPS module) <45dbA normal mode with typical load
<50dbA in battery mode
Environmental Ratings 0C to 40C operating (25C optimal for batteries)
-25C to +55C transient
5% to 95% relative humidity, non-condensing
2,000 meters elevation above sea level max
System will function at reduced performance outside the operating range.
Dimensions & Weights
(all are 2U 3.5" H x 17.5" W)
- UPS module 24.5" D, 92 lbs
- optional battery modules 24.5" D, 121 lbs
Warranty by Manufacturer - 2 years parts & labor
- 10 years pro-rated
Certifications

UL Listed, cUL, CE

NOTES:
1 - Oversized generators with automatic voltage regulators work best.
2 - This system will start most home refrigerator and freezer compressor motors.
3 - Under normal conditions batteries should last at least 3-5 years.  Replacement batteries are available and can be installed by user.
4 - Battery run-time is not linear.  At half the stated electrical load the run-time will be MORE than double the original value.

 

Optional Features available at additional cost

The following optional features can be ordering using the drop-down menus at the bottom of this page.  Click thumbnail images at right to enlarge.

External extended run-time battery module.  Up to 4 maximum can be added to UPS system.  Each module has short DC plug cord and connector on back to allow daisy-chaining together.

hups5125ebm.jpg (8889 bytes)

X-Slot SNMP/Web Adaptor Card for management of UPS through web interface.  UPS comes standard with software and serial cable but if you prefer remote control and monitoring through the web this card will do it.  Fits in X-slot in rear.  Includes built-in switch hub.

hups5125webcard.jpg (21849 bytes)

X-slot Relay Interface Card provides dry contact interface between UPS and any external contact operated device.  Individual form-C contacts provided for many UPS status conditions including utility failure, low battery, UPS alarm/Ok, or on bypass.  Can be used to initiate start of standby generator or to perform other external control functions.

hups5125relaycard.jpg (7081 bytes)

 

 

Item Number: HUPS51252K
Your Price: $1,613.00
Shipping Weight: 150 lbs.

This system can be shipped direct to you with free freight (to USA 48 state destinations).  Due to their weight the UPS, transformer and optional external battery modules ship by truck freight.  Two people are required to unload truck. This system normally ships 1-2 weeks after order acceptance.

switch:
external batteries:
x-slot card:
 

Home ] Lightning/Surge Protection ] Automatic Voltage Regulators ] Tripp Lite UPS Systems ] Large UPS Systems ] APC UPS Systems ] Best UPS Systems ] Powerware UPS Systems ] UPS Comparison ] Opti-UPS ] Whole House UPS Systems ] Toshiba UPS Systems ] UPS Reconditioning Services ] Data Center Accessories ]

Are YOU ready for the next power outage?

We welcome your feedback or questions.  Click here to contact us.
See our Terms & Conditions before using information or ordering from this web site.
Copyright © 1999-2007 NoOutage.com LLC.  All rights reserved.