| System AC Line Input Voltage |
230VAC nominal
min. selectable at 144, 163, 182, 201
max. selectable at 259, 264 |
| System AC Line Input Frequency |
60Hz +10% |
| Minimum AC Line Circuit Capacity |
20 amps 230VAC |
| Minimum Portable Generator Size (optional) |
4000 Watts rated with 20 amp
240VAC receptacle |
| System DC Input Voltage (battery bank) |
24 VDC nominal
20 VDC min. to 30VDC max. |
| Inverter Power Output Rating |
2400 Watts continuous @ 67F
4800 Watts surge for 5 seconds |
| System Output Power Rating |
1500 Watts max continuous per
115VAC leg
(do not exceed inverter ratings) |
| System output voltage (on inverter) |
115/230VAC +7%
modified sine wave |
| System output frequency (on inverter) |
60 Hz +0.3% |
| Automatic Transfer Time |
4-6 milliseconds |
| System efficiency near full load |
87% |
Approximate Battery Run-Time
@ 67F with new batteries
(see NOTE at table bottom) |
1000VA/900 watts average |
1.5 hours |
| 2000VA/1800 watts average |
0.7 hours |
| Battery Charger Rating |
30A at 24Vdc nominal (approx
750 watts) |
| Charger Acceptance Voltage |
selectable:
28.8VDC for wet cells
28.4VDC for gel cells |
| Charger Float Voltage |
selectable:
26.6VDC for wet cells
27.2VDC for gel cells |
Approximate Recharge Time
for discharged
battery bank
(see NOTE at table bottom) |
5 hours to 95% capacity |
| Indicators |
AC Line Power Avail |
Green LED |
| On Inverter Power |
Yellow LED |
Near Full load (continuous)
Overload Shutdown (flash) |
Red LED |
| Battery Charge State |
(3) LED |
| Certifications |
Most components are UL Listed or UL
Recognized. Inverter/Charger is not UL. |
| NOTE: Based on minimum
recommended battery bank size of (2) 108 amp-hour 12V deep cycle
batteries. If double the number of batteries are used, run-time will
more than double and recharge time will double. |